At the scale of a server room, you're estimating over an aggregate and probably want some overhead/room to expand.


At the scale of a small to medium colocation facility you define W per cabinet... Such as a typical 44U height cabinet in a row designed for front to back airflow. 5kW per cabinet would be a normal low range, up to 10-12kW. Then figure out your floor spacing and sq ft usage to determine how many cabinets.